Overview
The 400 kVA Dry Transformer is specifically engineered for the modernization of the CHE Scropoasa substation at 6.3 kV and 20 kV. It boasts maintenance-free epoxy resin insulation, a low-loss silicon steel core, and copper windings. This transformer operates using natural air cooling and allows for voltage adjustments of ±2x2.5%. It adheres to EN 60076 standards. Included accessories are a bidirectional trolley, temperature sensors, and an integrated temperature control system. The transformer is capable of handling substantial overloads and complies with the ECO Design Directive 548/2014. Comprehensive factory testing guarantees its high performance and reliability. For more information, please contact us.
Key Specifications
- Power Rating: 400 kVA
- Voltage Options:
6.3 kV Model: Primary 6.3 kV / Secondary 0.4 kV
20 kV Model: Primary 20 kV / Secondary 0.4 kV
- Cooling System: Natural air circulation
- Temperature Class: According to SR EN 60076-3
- Maximum Winding Over-temperature: 100°C
- Noise Level: 63 dB
- Insulation: A blend of epoxy resin and quartz powder for maintenance-free operation, moisture resistance, and fire safety.
- Core: Low-loss cold-rolled silicon steel with high magnetic permeability and minimal hysteresis and eddy current losses.
- Windings: Copper with epoxy resin insulation, providing high mechanical strength against short-circuit forces.
Technical Features
- Connection: Dyn-5
- Adjustment: Five-step adjustment with a ±2x2.5% range on the high-voltage side, performed when the transformer is de-energized.
- Insulation Level: F
- Environmental Conditions:
Maximum Ambient Temperature: +40°C
Minimum Ambient Temperature: -30°C
Altitude: <1200 meters
Humidity: <100% at 20°C
Seismic Resistance: 760±15 mmHg
Accessories
- Trolley: Includes bidirectional wheels with a locking mechanism.
- Temperature Sensors: At least three PT100 sensors.
- Temperature Control Unit: Integrated into the protection, signaling, and monitoring system
- Lifting Lugs: For easy handling
- Neutral Terminal: Accessible on the low voltage side for the 400 kVA, 6.3/0.4 kV transformer
Compliance
- Standards: EN 60076, CEI 60076 series, IEC 60185, DIN-VDE 0414-1
- ECO Design Directive: Fully compliant with Directive 548/2014 and its subsequent amendments.
Operational Flexibility
- Overload Capability:
10% overload for 1 hour
20% overload for 30 minutes
30% overload for 15 minutes
40% overload for 8 minutes
50% overload for 4 minutes
- Overexcitation Tolerance: Capable of operating with a maximum of 5% deviation from nominal voltage and frequency.
Testing
Each transformer undergoes comprehensive factory testing, including:
- Verification of transformation ratio
- Connection group validation
- Measurement of winding resistance
- Insulation resistance and absorption coefficient testing
- Dielectric loss angle tangent measurement
- Applied voltage and induced voltage tests
- Measurement of no-load and short-circuit losses
- Winding overheating and homopolar impedance measurement
- Noise level assessment
- Dielectric rigidity of the oil
For further details, technical support, or customized quotes, please contact our sales team. We are dedicated to delivering reliable, high-quality transformer solutions tailored to your specific needs. Reach out today to experience our outstanding service and expertise.
Hot Tags: 400 kva dry transformer, China 400 kva dry transformer manufacturers, suppliers, factory, transformer, Outdoor Indoor Cable Distribution Cabinet, Comprehensive Protection and Control Unit, MNS LV Withdrawable Switchgear, 10kV Heat Shrink Cable Termination, Two winding Voltage Regulation Distribution Transformer