Product Description
The GCK low voltage withdrawable switchgear is suitable for three-phase AC systems with a frequency of 50(60)Hz, rated voltages of 380(400)V and 660(690)V, and rated currents of up to 5000A. It is designed for use in three-phase four-wire and three-phase five-wire power systems. This switchgear is widely applied in power plants, substations, industrial and mining enterprises, high-rise buildings, airports, stations, docks, and broadcasting and television communication centers. It serves as a power distribution center for power generation, transmission and distribution, electrical energy conversion, and consumption, including both power control (PC) and motor control center (MCC) functions.
Key Features
Frame Structure
The GCK low voltage switchgear features a modular assembly structure. The entire frame is connected using self-tapping screws. It is constructed with C-shaped special profiles, using 2mm thick steel plates bent to a modular size of 25mm. The frame is reinforced with strong self-tapping screws during assembly, ensuring flexibility in assembly and durability of use.
Modular Design
The GCK switchgear is designed with a modular approach, dividing the cabinet into three zones: the top for the busbar area, the front for the electrical equipment area, and the rear for the cable exit area. Steel plates separate the electrical equipment area from the cable area to ensure normal operation of the circuits and prevent fault expansion. When electrical components are withdrawn from the cabinet, live parts inside the cabinet are not exposed, enhancing user safety. For feeder cabinets, the cabinet width is 600mm, accommodating up to 9 or 18 feeder circuits (18 circuits are suitable only for load units of 63A or below).
Switchgear Types
Based on usage, the switchgear can be classified into receiving cabinets, PC cabinets (Power Control Centers), MCC cabinets (Motor Control Centers), and capacitor compensation cabinets.
Interchangeable Drawers
Drawers of the same functional unit are interchangeable. In the event of a fault, the faulty drawer can be withdrawn and replaced with a spare, allowing for quick restoration of power and significantly reducing downtime, thereby improving equipment reliability.
Hybrid Design
The switchgear can be designed as a combination of fixed and withdrawable types or as fully withdrawable. This design retains the simplicity, practicality, and cost-effectiveness of fixed cabinets while incorporating the compact size, functionality, and ease of replacement of withdrawable drawers.
Mechanical Interlocking
To ensure safe operation and maintenance, the switchgear is equipped with mechanical interlocking mechanisms. These mechanisms are installed between the drawer units and the doors, as well as with the main switch, to enhance reliability.
Drawer Dimensions
The drawers in the switchgear come in four standard heights: 1-unit/2, 1-unit, 2-unit, and 3-unit. These drawers are lightweight, easy to assemble, and feature a rational layout with positions for operation, testing, and isolation.
N and PE Lines
The N and PE lines are located at the rear bottom of the switchgear. The PE line is connected to the cabinet frame, making cable connections more convenient and grounding more reliable.
Ventilation
Without compromising the protection level, the switchgear features a ventilation system at the top and the top and bottom ventilation doors.
Technical Parameters
|
Standards and Technical Specifications |
Low Voltage Assemblies with Type Testing |
IEC60439.1-2006 |
|
Switchgear and Controlgear |
GB7251.1-2005 |
|
|
Low Voltage Withdrawable Switchgear |
JB/T9661-1999 |
|
|
Complete Switchgear |
|
|
|
Overvoltage Category |
IV |
Ⅲ |
|
Pollution Degree |
3 |
|
|
Rated Operational Voltage (Ue) |
660V |
380V |
|
Rated Frequency |
50Hz |
|
|
Horizontal Busbar |
||
|
Rated Current (A) |
5000, 4000, 3150, 2500, 2000, 1000 |
|
|
Rated Short-time Withstand Current (KA/1s) |
80, 65, 50 |
|
|
Rated Peak Withstand Current (KA/0.1s) |
176, 140, 105 |
|
|
Vertical Busbar |
||
|
Rated Current |
1400A |
1000A |
|
Rated Short-time Withstand Current (KA) |
50 |
|
|
Rated Peak Withstand Current (KA) |
105 |
|
|
Enclosure Protection Level |
IP30, IP40 |
|
Hot Tags: gck lv withdrawable switchgear, China gck lv withdrawable switchgear manufacturers, suppliers, factory, GGD LV Withdrawable Switchgear, GCS LV Withdrawable Switchgear, Outdoor Indoor Cable Distribution Cabinet, low voltage switchgear, MNS LV Withdrawable Switchgear